Electrical connection
6.1 Safety instructions for electrical connection
Danger due to defective seals
When working on the device, seals at the doors, roof panels as well as front, rear and side
panels can be damaged. Operation with defective seals can result in death, serious injury or
material damage.
● Replace the defective seals before commissioning. Observe the environmental conditions
Injury caused by short circuit
Damaged cables, or their improper routing, can cause damage to property and personal injury.
● Only use cables that are completely intact and not damaged. Correctly route the cables. Do
● Make sure that a short-circuit cannot occur on the power cables due to failure of the
● Check the electrical connections after service work.
Danger caused by incorrect cable routing
Failure to use the supplied cable ducts for laying the cables can lead to flashovers. This can
result in death, serious injuries or material damage.
● To connect the cables between the cabinets, use the cable ducts and the cable entries on
Material damage caused by parts that can be magnetized
The use of magnetizable parts, e.g. ferrous cable clamps, is not permitted. Using parts and
components that can be magnetized can cause damage.
● Only use parts that consist of non-magnetic material.
Material damage caused by high transition resistances
Cables connected to the connection point that are not in compliance with the applicable
regulations represent a high electrical transition resistance that can cause thermal damage
(contact erosion) during operation.
● Tighten the screws with the required torque.
Damage caused by incorrectly shrinking cable terminations
If you are connecting the mains and motor-side power cables, when shrinking the cable
terminations, other control lines and fiber-optic cables in the surrounding cable channels can
become damaged.
● When shrinking, ensure not to damage cables in the surrounding cable channels.
60
stated in the technical data.
not interchange input and output terminals.
insulation as a result of incorrect cable installation.
the roof. Lead the cables from here to the next cabinet.
SINAMICS SL150 6SL39616RC100AA02
Operating Instructions Rev.201910281458 EXAMPLE