Outdoor unit installation place

- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Category
4 sides are walls
Only 2 sides are
walls
Limitations on the
height of the wall
(Refer to 4 side
walls)
Installation Space
Front
No limit to the
height of the wall
Front
h
2
A
INSTALLATION PLACE
Case1
(10mm≤ Side
Space ≤49mm)
A≥10
B≥300
C≥10
D≥500
A≥10
B≥300
• The height of the wall on the front side
must be 1500mm or less.
• The height of the wall on the intake side
must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front
and the side are higher than the limit,
h
there must be additional space on the
1
B
front and the side.
- Additional Space on the intake side by
1/2 of h1.
- Additional Space on the front side by 1/2
of h2
- h2 = A(Actual height) - 1500
- h1 = B(Actual height) - 500
11
Case2
(Side Space
≥49mm)
A≥50
B≥100
C≥50
D≥500