Startup Settings and Maintenance

PC Setup
Communications
Programming
port
Console setting
Peripheral port
144
Bits:
145
Bits:
150
Bits:
RS-232C port
160
Bits:
161
Bits:
166
Bits:
PC System Menu
1,2,3...
6-4
Startup Settings and Maintenance
6-4-1
Hot Start/Hot Stop Functions
Operating Mode Change
Name
address
Serial communica-
tions mode
8 to 11
Baud rate
0 to 7
NT Link mode
maximum unit
0 to 3
number
Serial communica-
tions mode
8 to 11
Baud rate
0 to 7
NT Link mode
maximum unit
0 to 3
number
Note Set the baud rate to 115,200 bps when making settings with the CX-Program-
mer.
Set the PT as follows:
1. Select NT Link (1:N) from Comm. A Method or Comm. B Method on the
Memory Switch Menu under the System Menu on the PT Unit.
2. Press the SET Touch Switch to set the Comm. Speed to High Speed.
This section describes the following functions related to startup and mainte-
nance.
• Hot Start/Hot Stop Functions
• Startup Mode Setting
• RUN Output
• Power OFF Detection Delay Setting
• Clock
• Program Protection
• Remote Programming and Monitoring
Hot Start
Turn ON the IOM Hold Bit (A50012) to retain all data* in I/O memory when the
CPU Unit is switched from PROGRAM mode to RUN/MONITOR mode to start
program execution.
Settings
Default values
contents
02 Hex: NT Link
00 Hex: Host Link
(1:N mode)
00 to 09 Hex:
00 Hex: Standard
Standard NT Link
NT Link
0A Hex: High-
speed NT Link
(see note 1)
0 to 7 Hex
0 Hex (Max. unit
No. 0)
02 Hex: NT Link
00 Hex: Host Link
(1:N mode)
00 to 09 Hex:
00 Hex: Standard
Standard NT Link
NT Link
0A Hex: High-
speed NT Link
(see note 1)
0 to 7 Hex
0 Hex (Max. unit
No. 0)
Section 6-4
Other conditions
Turn ON pin 4 on
the CPU Unit DIP
switch.
---
Turn OFF pin 5 on
the CPU Unit DIP
switch.
---
229