4 Firmware Drive Functions
4.5 Output of manipulated variables
4.5.3
Manipulated voltage limitation
5475
OUTPUT_VOLTAGE_LIMIT
Manipulated voltage limitation
Unit:
Default:
V
10.0
Manipulated
variable inversion
5476
OUTPUT_VOLTAGE_INVERSION
Manipulated variable inversion
Bit 0= 0: No inversion
1: Inversion
Unit:
Default:
–
0
4-132
SINUMERIK 840D/SIMODRIVE 611 digital Descr. of Functions HLA Module (FBHLA) – 04.00 Edition
Minimum:
Maximum:
1.0
10.0
The manipulated variable setpoint is limited in the positive and negative direc-
tions to the value set in MD 5475 before the D/A conversion. An identical value
is set for both limits. A ZK3 message (can be interrogated via PLC) is activated
when the limitation is violated.
Minimum:
Maximum:
0
1
The voltage output (manipulated variable) can be inverted in machine data MD
5476 in order to compensate for differences in sign in the piping or wiring. Alter-
natively, the wiring of the manipulated variable for the valve could be altered.
Definition of direction: See Section 3.9.1.
Cross ref.: –
Relevant for:
Protection level:
HLA
3/3
Data type:
Effective:
FLOAT
Immediately
Cross ref.: –
Relevant for:
Protection level:
HLA
3/3
Data type:
Effective:
UNS.WORD
Immediately
Siemens AG 2000. All rights reserved