4 Firmware Drive Functions
4.5 Output of manipulated variables
4.5.2

Control output filter

5280
NUM_OUTPUT_FILTERS [n]
Number of control output filters
Unit:
Default:
0
5281
OUTPUT_FILTER_TYPE [n]
Type of control output filter
Unit:
Default:
0
5284
OUTPUT_FIL_1_FREQ [n]
Natural frequency of control output filter 1
Unit:
Default:
Hz
1000.0
4-130
SINUMERIK 840D/SIMODRIVE 611 digital Descr. of Functions HLA Module (FBHLA) – 04.00 Edition
0...7 index of the parameter set
Minimum:
Maximum:
0
1
The number of control output filters must be set in this machine data.
Table 4-6
Selecting the number of control output filters
0
No filter(s) active (default)
1
Filter(s) activated
Note
Before the filter type is configured, the corresponding filter machine data must
be parameterized.
0...7 index of the parameter set
Minimum:
Maximum:
0
1
The type of control output filter is entered in this machine data.
Table 4-7
Type of control output filter
0
Bit 0
Bit 0
1
0...7 index of the parameter set
Minimum:
Maximum:
10.0
8000.0
The filter key data are defined in MD 5284, MD 5285 and MD 5288 to MD 5290.
Input of natural frequency for control output filter 1 (PT2 low-pass). Setting a
value of <10 Hz for the natural frequency of the low pass initializes the filter as a
proportional element with a gain of 1, irrespective of the associated damping.
Relevant for:
HLA
Data type:
UNS.WORD
Relevant for:
HLA
Data type:
UNS.WORD
Low pass (see MD 5284/5285)
Band-stop (see MD 5288/5289/5290)
Relevant for:
HLA
Data type:
FLOAT
 Siemens AG 2000. All rights reserved
08.99
02.99
Cross ref.: –
Protection level:
3/3
Effective:
Immediately
Cross ref.: –
Protection level:
3/3
Effective:
Immediately
Cross ref.: –
Protection level:
3/3
Effective:
Immediately