Run Times of the FCs and FBs for Redundant I/O

Table 13-1 Run times of the blocks for redundant I/O
Block
FC 450 RED_INIT
Specifications are
based on the startup
FC 451 RED_DEPA
FB 450 RED_IN
Invoked from the
corresponding
sequence level.
FB 451 RED_OUT
Invoked from the
corresponding
sequence level.
13-10
Run time in single/single mode
m
2 ms + 300
s / configured module
pairs
The specification for a module pair is a
mean value. The run time may be <
m
300
s for a few modules. For the
great majority of redundant modules
the value may even be > 300
m
160
s
m
m
750
s + 60
s / module pair of the
current TPA
The specification for a module pair is a
mean value.
The run time may be additionally
increased if discrepancies occur
resulting in passivation and logging to
the diagnostics buffer.
The run time may also be increased by
a depassivation carried out in the
individual sequence levels of FB
RED_IN. Depending on the number of
modules in the sequence level, the
depassivation may increase the run
time of the FB RED_IN by 0.4 to 8 ms.
An 8 ms increase can be expected in
redundant operation of modules
totalling more than 370 pairs of
modules in a sequence level.
m
m
650
s + 2
s / module pair of the
current TPA
The specification for a module pair is a
mean value. The run time may be < 2
m
s for a few modules. For the great
majority of redundant modules the
m
value may even be > 2
s.
Run time in redundant mode
m
s.
m
360
s
m
m
1000
s + 70
current TPA
The specification for a module pair is a
mean value.
The run time may be additionally
increased if discrepancies occur
resulting in passivation and logging to
the diagnostics buffer.
The run time may also be increased by
a depassivation carried out in the
individual sequence levels of FB
RED_IN. Depending on the number of
modules in the sequence level, the
depassivation may increase the run
time of the FB RED_IN by 0.4 to 8 ms.
An 8 ms increase can be expected in
redundant operation of modules
totalling more than 370 pairs of
modules in a sequence level.
m
m
860
s + 2
s / module pair of the
current TPA
The specification for a module pair is a
mean value. The run time may be < 2
m
s for a few modules. For the great
majority of redundant modules the
value may even be > 2
Automation System S7-400H Fault-tolerant Systems
s/ module pair of the
m
s.
A5E00068197-07