Protection Levels Of A S7-400 Cpu; Operating Sequence For Memory Reset; Cold Restart - Siemens SIMATIC S7-400H Manual

Automation system, fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Table 4-3
Protection
Level
1
2
3
If different protection levels are set with the mode selector and with STEP 7, the
higher protection level applies (3 before 2, 2 before 1).

Operating Sequence for Memory Reset

Case A: You want to download a complete, new user program to the CPU.
1. Turn the switch to the STOP setting.
Result: The STOP LED lights up.
2. Turn the switch to MRES, and keep it in this position.
Result: The STOP LED is dark for a second, light for a second, dark for a
second and then remains on.
3. Turn the switch back to STOP, and then within the next 3 seconds turn it back
to MRES and then back to STOP.
Result: The STOP LED flashes for at least 3 seconds at 2 Hz (memory reset is
executed) and then lights up continuously
Case B: When the STOP LED flashes slowly at 0.5 Hz, the CPU is requesting
a memory reset (system memory reset request, after a memory card has
been removed or inserted, for example).
Turn the switch to MRES and back to the STOP position.
Result: The STOP LED flashes for at least 3 seconds at 2 Hz (a memory reset
is executed) and then lights up continuously.
You can find the complete description of what happens during a memory reset in
the: S7-400, M7-400 Programmable Controllers Installation Manual, Chapter 6.

Cold Restart

Following a cold restart, the user program starts from the beginning again. All the
data, including the retentive data, are deleted.
Automation System S7-400H Fault-tolerant Systems
A5E00068197-07

Protection levels of a S7-400 CPU

All programming device functions are permitted
(default setting).
It is permissible to load objects from the CPU into
programming device. In other words, only read
programming device functions are permitted.
Functions for process control, process monitoring
and process communication are permitted.
All information functions are permitted.
Functions for process control, process monitoring
and process communication are permitted.
All information functions are permitted.
Installation of a CPU 41x-H
Function
Switch Position
RUN-P/STOP
RUN
4-13