LTPH-UM-1237-04
I
A
DENTIFYING
LARMS
Alarm relay contacts for each management unit are on J13 and J14
and an alarm monitoring device per local practice.
Alarm relay pins (J14)
T
U
URNING
P THE
Perform the following procedures prior to installing the management unit(s) into the shelf.
Insert Fuse
Insert an appropriately sized fuse(s) into the equipment bay fuse panel for the circuit(s) where the HRM-238 shelf
battery wire(s) were terminated. Refer to the appropriate management unit user manual for power consumption,
power dissipation, and current drain.
HRM-238 List 1
Figure 11. Alarm Relay Wire-Wrap Pins
Table 7. Alarm J13 and J14 Pinouts
Pin
Description
1
CRIT_AUD_NC_A
2
CRIT_AUD_COM_A
3
CRIT_AUD_NO_A
4
CRIT_VIS_NC_A
5
CRIT_VIS_COM_A
6
CRIT_VIS_NC_A
7
MAJ_AUD_NC_A
8
MAJ_AUD_COM_A
9
MAJ_AUD_NO_A
10
MAJ_VIS_NC_A
11
MAJ_VIS_COM_A
12
MAJ_VIS_NO_A
S
YSTEM
(Figure
Table 7
describes the alarm J13 and J14 pinouts.
Alarm relay pins (J13)
Pin
Description
13
MIN_AUD_NC_A
14
MIN_AUD_COM_A
15
MIN_AUD_NO_A
16
MIN_VIS_NC_A
17
MIN_VIS_COM_A
18
MIN_VIS_NO_A
19
SYS_ID_NC_A
20
SYS_ID_COM_A
21
SYS_ID_NO_A
22
EXT_ACO_A
23
LGND
July 21, 2004
11). Install wiring between these pins
H0651-A
Installation
11