Installing the AppController
Set the appropriate jumpers on the AppController.
2
To use...
IN-1
IN-1
IN-2
All
Rnet Port
Connect the analog output wiring to the screw terminals on the AppController and to the controlled device.
3
AppController
Installation and Start-up Guide
For...
Thermistor
0–5 Vdc
Thermistor/
Dry contact
Thermistor
Dry contact
ZS sensors
Wireless Adapter for
wireless sensors
Equipment Touch
TruVu™ ET Display
10
Set jumpers IN-1 to the Therm position.
Set jumpers IN-1 to the 0-5 Vdc position.
Set jumpers IN-2 to the Thermistor/Dry contact position.
Verify the IN-5 jumper is on.
Set the Rnet jumper to Rnet.