Viessmann VITOCROSSAL 200 Installation Instructions Manual page 31

Type cm2c
Hide thumbs Also See for VITOCROSSAL 200:
Table of Contents

Advertisement

Gas connection
(cont.)
3.
Fig. 25
1. Break out the aperture for the gas line at the perfo-
ration in the right or left-hand side panel. Use pro-
tective gloves.
2. Route the gas line through the aperture in the side
panel.
3. Secure the inner fascia to the side panel with two
screws
.
qR
2.
1.
4. Connect the gas supply according to TRGI 2008
[or local regulations].
AT: Connect the gas supply according to
ÖVGW-TR Gas 1996 and the regionally appli-
cable building regulations.
CH: Connect the gas supply according to SVGW.
Note
According to the [German] Combustion Ordinance,
a thermally actuated shut-off device must be instal-
led in the gas line. Outside the boiler, a manual gas
shut-off device must be provided (not part of the
standard delivery).
Note
If the gas line has been contaminated (e.g. old
pipes with corrosion products), we recommend
installing a gas filter in the supply line.
Max. permiss. gas supply pressure 50 mbar
(5 kPa)
Gas connection:
Rated heating output
186 kW
246 kW
Connection
R 1
R 1
¼
31