Mains Monitor - Viessmann Vitocal 300-G Pro Series Installation And Service Instructions For Contractors

84.8 to 222.0 kw brine/water heat pumps, 2-stage
Table of Contents

Advertisement

Mains monitor

Electronic soft starter, type SMC
Electronic soft starter functions:
Monitoring the compressor mains feed
Reducing the compressor starting current during the
starting procedure
Delivered condition:
Rotating field, phase asymmetry: 20 %
Max. compressor operating current "Imax": Subject
to compressor output
Overload protection
If the tolerance ranges of the electronic soft starter are
exceeded, the soft starter will automatically separate
the appliance from the mains.
Remove the cause if the relay has responded. The
relay does not need to be reset.
Starting characteristics
The starting characteristics are set at the DIP switches
behind the transparent protective flap of the electronic
soft starter. At the factory, the DIP switches are set to
suit the respective heat pump type.
Prior to commissioning, compare the DIP switch set-
tings with the details in the separate "Connection and
wiring diagram", and adjust if necessary.
LED explanation
L1
L2
HOLD TO TEST
PUSH TO RESET
SMC-3
OVLD SETTING
LED STATUS
ON
RUN/ON
RUN/FAULT
1
OLVD
2
TEMP
3
PHASE REVERSAL
4
PHASE LOSS/OPEN LOAD
5
PHASE IMBALANCE
6
SHORTED SCR
7
TEST
A1 A2 IN1 IN2 97 98 13 14
T1
T2
Fig. 35
LED lights up:
Mains monitoring active
LED flashes: Fault
Number of flashes:
1 Overload
2 Excess temperature
3 Phase reversal
4 Phase loss / motor not connected
5 Phase asymmetry
6 Short-circuited thyristor
7 Test
Installation sequence
L3
T3
47