Limit Values Of Inputs And Outputs - Siemens 7XR61 Series Short Directions For Use

Coupling unit
Table of Contents

Advertisement

Available languages

Available languages

7XR6100-0*A00

Limit values of inputs and outputs

Auxiliary voltage
Rated auxiliary voltage U
Permissible variations ac
Load capability of the capacitive coupling circuit
Connections (4A1 - 4B1)
Permissible voltage, continuous
R.M.S. value of voltage
R.M.S. value of current
Test voltage
Output ratings
(Short circuit on 4A1 and 4B1)
Continuous
Output (1B1 - 1B3)
Output (1B1 - 1B4)
*) Don't use the internal resistors in case of higher currents. In the event of a large harmonics
content in the rotor voltage an external series resistor, type 3PP1336-0DZ-013002 is
recommended for the protection of the coupling capacitors (refer connection example 2).
C53000-B119U-C124-1
ac
100 to 125 V ac, 50/60 Hz
H
80 to 144 V ac
3.15 kV dc
220 V~ (≤ 50 Hz)
≤ 0.2 A *) continuously
4.7 kV dc for ≤ 2 s
100 mA (without choke)
175 mA (with choke) max. 1 h
230 mA max. 0.5 h
English
230 V ac, 50/60 Hz
176 to 265 V ac