7XT3400-0*A00/DD
Limit values
Load capability of the 20Hz band-pass filter
Connections (1B1 - 1B4)
Permissible voltage, continuous
Permissible voltage for ≤ 30 s
Frequency of superimposed ac voltage
Overload capability, continuous
Test voltage
Load capability of the voltage divider circuit
Connections (1A1 - 1A4):
Permissible voltage, continuous
Permissible voltage for < 30 s
Test voltage
Permissible ambient temperatures
with RB <5 Ω burden
with RB >5 Ω burden
Note: The device may produce up to 75 W power losses during service. In order to prevent
heat pockets, the dissipation of the losses must not be restricted. The minimum clearance
above and below the device to other units or walls is 100 mm or 4 inches. In cubicles, the
device shall be installed in the bottom area.
C53000-B119U-C130-1
55 V ac
550 V ac
≥ 45 Hz
3.25 A ac
2.8 kV dc
55 V ac
550 V ac
2.8 kV dc
≤ 40 °C or ≤ 104 °F
≤ 55 °C or ≤ 131 °F