Error Code Guide - Navien NR-10P User Manual

Table of Contents

Advertisement

Problem
Possible Cause(s)
Is the system running for domestic
hot water (DHW)?
Space Heating
side malfunction
(DHW)
Is the pre-heating icon blinking on
the remote controller?
46
What to do
When the unit is heating for DHW, the heating
side does not work.
there is a standby time between switching
form DHW and heating (3 min).
When the unit is in "pre-heating" mode the
heating side is placed into stand by.

Error Code Guide

Error Code
Reason
Water is boiling inside the heat
E001
exchanger.
Low pressure on heating side.
E002
Ignition failure.
E003
False flame detection.
E004
Space Heating supply :
E005
Thermostat-open
Space Heating supply :
E006
Thermostat -closed
DHW Hot water supply:
E007
thermostat -open
Self-diagnostic / Action
1. Clean the inlet water strainer (part#25).
2. Check the heat exchanger; remove
and clean with a cleaning solution.
1. Turn off the system.
2. Turn the unit back on.
1. Check to see if the main gas supply valve is open.
2. Check that the power is "ON".
3. Check the igniter for spark (part#18).
1. Ensure ground wire is connected.
2. Check the igniter for spark.
1. Check the thermostat.
2. Replace the thermostat.
1. Check the thermostat.
2. Replace the thermostat.
1. Check the thermostat.
2. Replace the thermostat.
47