10 - CONNECTIONS
Connection diameters:
Cooling coil
Heating coil
Always use two spanners when connecting or tightening the hydraulic couplings to avoid twisting the pipes and applying stress on the
welds.
To avoid the risk of condensation, the hydraulic pipes and elements must be carefully insulated.
Before insulating, check the tightness of the couplings.
Warning
: the operating pressure on the chilled or hot water network must not exceed 8 bar.
Once all the connections have been made, the access holes must be sealed.
Insulated flexible connections are available on request for carrying out hydraulic connections. Ensure these are not bent too acutely 
to avoid pinching the inner tube and restricting the flow of water.
Condensate drain
The condensate drain pan should include a siphon to avoid any risk of overflowing. 
(See position and connection diameter on the dimensional drawing).
In these units, the pan is depressed due to its position in relation to the fan motor assembly.
To enable correct drainage, the height must be equal to at least twice the unit's depression.
A condensate drain pump option is available (see technical specifications), provided that the humidifier option has not been requested.
If the humidifier option is selected, the discharge must not drain into the unit's drain pan. To have a single discharge for both, connect 
the humidifier drain downstream of the unit's drain pan.
Warning: the condensates from the humidifier can reach 100 °C.
10.2 - Electrical connection
The electrical connections and wiring must be set up as shown on the wiring diagram included with the unit and in accordance with
applicable standards and regulations.
The unit's power supply cable must be determined according to the power of the unit, the length of the cable, the protection, and the
operating mode.
Check that the characteristics of the electrical power supply conform with the indications on the name plate.
Please ensure the unit is connected to earth, and that the power supply is always able to supply the necessary power.
W40
Inlet
G 1"1/4 (M)
Outlet
G 1"1/4 (F)
Inlet
Outlet
W53
W78
G 1"1/4 (M)
G 1"1/2 (M)
G 1"1/4 (F)
G 1"1/2 (F)
W40
W53
G 3/4" (M)
G 3/4" (M)
G 3/4" (M)
G 3/4" (M)
67
W100
W115
G 1"1/2 (M)
G 1''1/2 (M)
G 1"1/2 (M)
G 1''1/2 (F)
W78
W100
G 3/4" (M)
G 3/4" (M)
G 3/4" (M)
G 3/4" (M)
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50co w5350co w4050co w10050co w11550co w78

Table of Contents