Under Ceiling Type

Wireless remote control

1
Procedure
Turn on the circuit breaker of the air conditioner.
The operation is not accepted for 5 minutes when
circuit breaker is turned on at first time after installation,
and 1 minute when circuit breaker is turned on at the
next time and after. After the specified time has
passed, perform a test operation.
2
Procedure
Push "ON/OFF" button on the remote control, select
[COOL] or [HEAT] with "MODE" button, and then select
[HIGH] with "FAN" button.
3
Procedure
Cooling test run
Set the temperature to 64°F
(18°C) with the temp. setup
buttons.
4
Procedure
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 66 °F (19°C)
with the temp. setup buttons.
5
Procedure
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 64 °F (18°C)
with the temp. setup buttons.
6
Procedure
4
5
Repeat procedures
Indicators "Operation" (green), "Timer" (green), and
"Ready" (orange) in the wireless receiver section flash
in approx. 10 seconds, and the air conditioner starts
operation. If any of these indicators does not flash,
repeat procedures
2
5
to
.
7
Procedure
Upon completion of the test run, push "ON/OFF" button
to stop operation.
<Overview of test run operations using the
wireless remote control>
▼ Cooling test run:
ON/OFF → 64 °F (18 °C) → 66 °F (19°C) → 64 °F
(18°C) → 66 °F (19°C) → 64 °F (18°C) → 66 °F (19°C)
→ 64 °F (18°C) → (test run) → ON/OFF
Heating test run
Set the temperature to 86 °F
(30°C) with the temp. setup
buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 84 °F (29°C)
with the temp. setup buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 86 °F (30°C)
with the temp. setup buttons.
4
5
.
▼ Heating test run:
ON/OFF → 86 °F (30°C) → 84 °F (29°C) → 86 °F
(30°C) → 84 °F (29°C) → 86 °F (30°C) → 84 °F (29°C)
→ 86 °F (30°C) → (test run) → ON/OFF
Always select
[HIGH] fan
speed.