Toshiba CARRIER RAV-SP180CT-UL Installation Manual page 23

Air conditioner (split type) indoor unit under ceiling type
Table of Contents

Advertisement

Under Ceiling Type
5
Procedure
Push
button. In this time, if the display changes
from flashing to lighting, the setup completes.
• To change the setup of an indoor unit other than the
selected one, start operation from Procedure
• To change the setup of another setup in the selected
indoor unit, start operation from Procedure
Pushing
button clears the set up contents which
have been already set. In this case, retry from
2
Procedure
.
6
Procedure
When settings have been completed, push
to determine the settings.
When
button is pushed, "SETTING" flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote control is accepted.)
Installation to high ceiling
When the height of the ceiling to be installed exceeds
3.5 m (11'6"), adjustment of fan speed is necessary.
Set up the high ceiling.
• Set according to the basic operation procedure
1
2
3
4
5
(
• Item code in Procedure specifies [5d].
• Select [SET DATA] in Procedure from "List of
installable ceiling height" in this Manual.
• For the item code in Procedure
• For the SET DATA in Procedure
data of static pressure to be set up from the table on
the right.
(Exchange by wired remote control)
SET DATA
Standard
0000
(Factory default)
0001
High static pressure 1
2
.
3
.
button
6
).
3
, specify [5d].
4
, select the setup
11'6" (3.5 m) or less
more than 11'6" (3.5 m)
up to 13'1" (4.0 m)
– 22 –
Using wireless remote control
Change the high ceiling setting with the DIP switch on
the P.C. board of the signal receiving part.
Refer to the installation manual of the wireless remote
controller kit for the details.
High ceiling setting can be changed by arranging the
jumper block on the indoor unit micro computer P.C.
board as shown in the table below as well.
* However, once the setting is changed, it is
necessary to reset the setting back to 0000 that
placing the jumper block back to the factory default
position and rewriting the setting data back to 0000
with wired remote control (sold separately). (The
setting can be changed to 0001, 0003 and 0006
without resetting.)
• Select by exchange of jumper block on indoor
microcomputer P.C. board.
jumper block
position
SET DATA
Short
Open
0000
0001
• Jumper block position
(CN112, CN111, CN110 from the left)
Installation Manual
Note
Standard filter
(Factory default)
High static pressure 1
EN
22-EN