Under Ceiling Type
Using attached installation pattern
Installation pattern
Using the pattern, positioning of the hanging bolt and
pipe hole can be performed.
* As an error to some degree may generate on the
pattern size due to temperature and humidity, be
sure to confirm the size.
Installation of hanging bolts
Use 3/8" (M10) hanging bolts (4 pcs, to be local
procure).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.
Install the bolts with insert brackets or anchor bolts.
(Blade type
bracket)
Steel flame structure
Use existing angles or install new support angles.
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Draw-out direction of pipe/
wire
• Decide installation place of the unit and draw-out
direction of pipe and wire.
9-EN
Ceiling surface
Wall face
New concrete slab
Rubber
Anchor bolt
(Slide type
(Pipe hanging
bracket)
anchor bolt)
Hanging bolt
Hanging bolt
Support angle
Pipe knockout hole
• Piping from rear side
* Cut off the groove section with a plastic cutter, etc.
Grooves
• Piping from right side
* Cut off the groove section with a metal saw or
plastic cutter, etc.
• Piping from left side
Taking pipe from left side is applied only to the
drain pipe.
The refrigerant pipe cannot be taken out from the
left side.
* Cut off the groove section with a metal saw or
plastic cutter, etc.
Groove
• Piping from upper side
Taking pipe from upper side is applied only to
the refrigerant pipe.
When taking out the drain pipe from the upper
side, use a drain up kit sold separately.
Open the upper pipe draw-out port (Knockout hole)
shown in the external view.
(Knockout hole of thin plate)
After piping, cut off the attached thermal insulator of
the top plate to pipe shape, and then seal the
knockout hole.
– 9 –
Installation Manual
Rear cover
100
Opened when
refrigerant pipe is
taken out from the
rear side
Opened when only drain pipe is
taken out from the rear side
Groove
Side panel (Right side)
Side panel (Left side)