Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Field
Function
SYSTEM SETUP ( ✱ 20– ✱ 29)
∗ 20
INSTALLER CODE
✱ 21
QUICK ARM ENABLE
✱ 22
RF JAM OPTION
✱ 23
FORCED BYPASS
∗ 24
RF HOUSE ID CODE
✱ 26
CHIME BY ZONE
✱ 27
X–10 HOUSE CODE
✱ 28
ACCESS CODE FOR
4285/4286 PHONE MODULE
✱ 29 LONG RANGE RADIO OUTPUT
ZONE SOUNDS AND TIMING ( ✱ 31 – ✱ 39)
✱ 31
ONE AUDIBLE ALARM PER ZONE
✱ 32
FIRE ALARM SOUNDER TIMEOUT
✱ 33
ALARM SOUNDER TIMEOUT
✱ 34
EXIT DELAY
✱ 35
ENTRY DELAY #1 (zone type 01)
✱ 36
ENTRY DELAY #2 (zone type 02)
∗37
AUDIBLE EXIT WARNING
✱ 38
CONFIRMATION OF ARMING DING
✱ 39
POWER UP IN PREVIOUS STATE
DIALER PROGRAMMING ( ✱ 40 – ✱ 42)
Enter the number of digits shown. Do not fill unused spaces. Enter 0–9; #+11 for ' ✱ '; #+12 for '#'; #+13 for a 2-second pause.
∗40
PABX ACCESS CODE
∗41
PRIMARY PHONE No.
∗42
SECOND PHONE No.
352*5$00,1*)250
Data Entries
|
|
Part. 1 Part.2
[0]
Part. 1 Part. 2
|
Part. 1 Part. 2 Common
[0]
[0]
|
[00]
(Partition 1 only)
[0]
[0]
[0]
[1]
|
Part. 1 Part. 2
|
Part. 1 Part. 2
|
Part. 1 Part. 2
Part. 1 Part. 2
Part. 1 Part. 2
[1]
|
|
Enter up to 6 digits. If fewer than 6 digits are entered, exit by pressing [✶] and next
desired field number. To clear entries from field, press ✱40✱ .
|
|
|
|
|
|
|
Enter up to 20 digits; Do not fill unused spaces. If fewer than 20 digits entered, exit by pressing [✶] and
next desired field number. To clear entries, press ✱ 41 ✱ .
|
|
|
|
|
|
|
Enter up to 20 digits; Do not fill unused spaces. If fewer than 20 digits entered, exit by pressing [✶] and next
desired field number. To clear entries, press ✱ 42 ✱ .
Programmable Values
4 digits, 0–9
|
[6321]
0 = no; 1 = yes
[1,1]
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
0 = none UL: must be "0"
[1,1]
1 = bypass open zones
00 = disable all wireless touchpad usage
|
|
01–31 = using 5827, 5827BD or 5804BD touchpad
[00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3,
using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
for " ✱ ", or # + 12 for "#".
UL: must be "00" for UL Commercial Burg. installations
0 = disable; 1 = enable
0 = no UL: must be "0"; 1 = yes
0 = sounder stops at timeout;
1 = no sounder timeout UL: must be "1" for fire install.
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min;
4 = 16 min; UL: minimum "1" (4 min.)
00–99 = seconds of exit delay time for each partition
|
[60,60]
Common zones use same delay as partition 1.
00–99 = seconds of entry delay #1 time for each
|
[45,45]
partition; UL: 45 seconds max.
Common zones use same delay as partition 1.
00–99 = entry delay #2 time for each partition;
|
[90,90]
UL: 60 seconds max.
Common zones use same delay as partition 1.
0 = no; 1 = yes
[1,1]
0 = no; 1 = yes (wired touchpads and RF)
[0,0]
2 = yes, RF only
0 = no; 1 = yes UL: must be "1"
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
– 3 –
|
|
|
|
|
|
|
|