Activating the restriction of setting
Activating the restriction of setting
Local HMI
Activating the restriction of setting via local HMI can only be done from the local HMI.
Procedure
1.
Navigate the menus to:
Configuration/BuiltInHMI/SettingRestrict
2.
Set SettingRestrict = Block.
Note!
The HMI--BLOCKSET functional input must be configured to the selected binary input before
setting the setting restriction function in operation. Carefully read the instructions.
Serial communication, change of active group
Activating the restriction of setting, or change of active group via the rear communication port,
can only be done from the local HMI.
Procedure
1.
Navigate the menus to:
Configuration/TerminalCom/SPACom/Rear/ActGrpRestrict
2.
Set ActGrpRestrict = Block
Serial communication, setting
Activating the restriction of setting or change of active group, can only be done from the local
HMI.
Procedure
1.
Navigate the menus to:
Configuration/TerminalCom/SPACom/Rear/SettingRestrict
2.
Set SettingRestrict = Block
Setting and configuring the terminal
Chapter 9