Testing the voltage difference

Set the voltage difference at 30% U1b on the HMI, and the test should check that operation is
achieved when the voltage difference UDiff is lower than 30% U1b.
The settings in
table
10can be used during the test if the final setting is not determined.
Table 10:
Test settings for voltage difference (NA=Not applicable)
Parameter
Operation
InputPhase
UMeasure
PhaseShift
URatio
USelection
AutoEnerg
ManEnerg
ManDBDL
UHigh
ULow
FreqDiff
PhaseDiff
UDiff
tAutoEnerg
tManEnerg
OperationSynch
ShortPulse
FreqDiffSynch
tPulse
tBreaker
VTConnection
tSync
FreqDiffBlock
U5
Activate SYN2_CB1CLD
UL1
Activate SYN3_CB2CLD
UL2
Activate SYN3_FD2CLD
U5
Activate SYN3_CB1CLD and CB2CLD
U4
No activation of inputs necessary
Setting
On
UL1
Ph/N
0 deg
1.00
SingleBus
Off
Off
Off
70% U1b
40% U1b
0,05 Hz
45 °
30% U1b
0.5 s
0.5 s
Off
Off
0.4 Hz
0.2 s
0.2 s
Line
Os
Off