3
3.1
3.2
3.3
3.3.1
Checking the self supervision signals
Checking the self supervision signals
Reconfiguring the terminal
I/O modules configured as logical I/O modules (BIM, BOM, IOM, DCM, IOPSM or MIM) are
supervised. Not configured I/O modules are not supervised.
Each logical I/O module has an error flag that is set if anything is wrong with any signal or the
whole module. The error flag is also set when there is no physical I/O module of the correct type
present in the connected slot.
Procedure
1.
Browse to the 'Reconfigure' menu.
The Reconfigure menu is located in the local HMI under:
Configuration/I/O-modules/Reconfigure
2.
Select 'Yes' and press 'E'.
Setting the terminal time
This procedure describes how to set the terminal time.
1.
Display the set time dialog.
Navigate the menus to:
Settings/Time
Press the E button to enter the dialog.
2.
Set the date and time.
Use the Left and Right arrow buttons to move between the time and date
values (year, month, day, hours, minutes and seconds). Use the Up and
Down arrow buttons to change the value.
3.
Confirm the setting.
Press the E button to set the calendar and clock to the new values.
Checking the self supervision function
Navigating the menus
This procedure describes how to navigate the menus in order to find the reason of an internal
failure when indicated by the flashing green LED of the HMI module.
Chapter 7
Energising the terminal
55