Download Print this page

Jumper Position; Led Indicator - Siemens FDCIO181-2 Product Manual

Advertisement

Jumper

LED indicator

5
Building Technologies
Fire safety and security products
No.
Signification
1
LEDs for the status indication of the in-/output
2
Jumper for the polarity of the monitoring for output 1
3
Connection output 1
4
Port for the connection of the 24V supply for output 1
5
Port for the connection of the 24V supply for output 2
6
Connection output 2
7
Jumper for the polarity of the monitoring for output 2
8
Port for the connection of the FD18-BUS detection line
9
Connection input 1
10
Connection input 2

Jumper position

If the configurations on the control panel and jumper don't match, this is recognized and an
error message is triggered.
Any other jumper position is not allowed.
For each in-/output, one red LED indicate the status.
LED
Off
Flashes every 1 s, 250ms on
Input 1 LED flashes every 1s, 2...5ms on
Fig.8 Overview
Signification
Output1 is not monitored.
Output1 is monitored.(factory default)
Output2 is not monitored.
Output2 is monitored.(factory default)
Signification
Normal operation, in/output is
monitored.
Input/output activated
Localization mode
A6V10214492_a_en_--