Advertisement

Connection

4.4 Disabling the Vdc-max controller

Integration of the thermostatic switch as release for switch-off via OFF2
The thermostatic switch must be connected to a free digital input of the SINAMICS G130 so
that the converter is safely disconnected from the power supply if the braking resistor
overheats. A digital input on the TM31 Terminal Module, on the TB30 Terminal Board or on
the Control Unit can be used for this.
Subsequently the digital input must be used as release for a switch-off with OFF2. External
fault 2). The interconnection can be made with the STARTER or via the AOP30.
Table 4- 7
Parame-
ter
p2107
Table 4- 8
Parame-
ter
p2107
4.4
Disabling the Vdc-max controller
The Vdc-max controller must be switched off (p1240 = 0) when a brake chopper is used.
36
Parameterizing the connection of the thermostatic switch at digital input 16 at the
CU320-2 Control Unit
Sink
Description
BI: External fault 2
Parameterizing the connection of the thermostatic switch at digital input 11 at Terminal
Module TM31
Sink
Description
BI: External fault 2
DO
Parame-
ter
Vector
r0722.16
CU digital inputs
DI 16 (X122.5 / X120.3)
DO
Parame-
ter
Vector
r4022.11
TM31 digital inputs
DI/DO 11 (X541.5)
Operating Instructions, 11/2017, A5E00331454A
Source
Description
DO
CU
Source
Description
DO
TM31
Braking Module / braking resistor