Parameter list
8.2 Parameter list
Parameter
Function
P0701[0...2]
Function of digital input 1 0 - 99
Selects function of digital input 1.
0
1
2
3
4
5
9
10
11
12
13
14
15
16
17
18
22
23
24
25
27
29
33
99
Dependency:
Resetting 99 (enable BICO parameterization) requires:
P0700 command source or
P0010 = 1, P3900 = 1, 2 or 3 (quick commissioning) or
P0010 = 30, P0970 = 1 factory reset in order to reset
Note:
"ON/OFF1" can only be selected for one digital input (e.g. P0700 = 2 and P0701 = 1). Configuring DI2
with P0702 = 1 will disable digital input 1 by setting P0701 = 0. Only the last activated digital input serves
as a command source. "ON/OFF1" on a digital input can be combined with "ON reverse/OFF1" on another
digital input.
P0702[0...2]
Function of digital input 2 0 - 99
Selects function of digital input 2.
See P0701.
P0703[0...2]
Function of digital input 3 0 - 99
Selects function of digital input 3.
See P0701.
224
Range
Factory
default
0
Digital input disabled
ON/OFF1
ON reverse/OFF1
OFF2 - coast to standstill
OFF3 - quick ramp-down
ON/OFF2
Fault acknowledge
JOG right
JOG left
Reverse
MOP up (increase frequency)
MOP down (decrease frequency)
Fixed frequency selector bit0
Fixed frequency selector bit1
Fixed frequency selector bit2
Fixed frequency selector bit3
QuickStop Source 1
QuickStop Source 2
QuickStop Override
DC brake enable
Enable PID
External trip
Disable additional freq setpoint
Enable BICO parameterization
0
9
Can be
Scaling
Data
changed
set
T
-
CDS U16
T
-
CDS U16
T
-
CDS U16
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
Data
Acc.
type
Level
2
2
2