Setting An Ahu Kit Address (Main/Rmc) - Samsung MCM-D201N Installation Manual

Ahu kit
Table of Contents

Advertisement

Setting an address and installation option of AHU KIT

Setting an AHU KIT address (MAIN/RMC)

1. Check whether power is supplied or not.
- When the AHU KIT is not plugged in, there should be additional power supply.
2. The reception part of a remote controller is built in the AHU KIT PBA.
3. Each address of AHU KIT(MAIN/RMC) should be set according to installation conditions.
4. Assign each AHU KIT address(MAIN/RMC) with a remote controller.
- The default setting value of an AHU KIT address(MAIN/RMC) is "0A0000-100000-200000-300000".
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
Explanation
PAGE
Remote
Controller
Display
Indication
Details
Indication
and Details
0
Option
SEG7
Explanation
PAGE
Remote
Controller
Display
Indication
Details
Indication
and Details
1
• When "A"~"F" is entered to SEG5~6, the main address of AHU KIT will not be changed.
• If you set the SEG 3 as 0, the AHU KIT will maintain the existing MAIN ADDRESS even if you have entered the
CAUTION
option value of SEG5~6.
• If you set the SEG 9 as 0, the AHU KIT will maintain the existing RMC ADDRESS even if you have entered the
option value of SEG11~12.
22
SEG2
SEG3
MODE
Setting Main address
Indication
Details
Indication
0
A
1
SEG8
SEG9
Setting RMC address
-
Indication
0
1
SEG4
Hundreds' digit of an
address
Details
Indication
Details
No Main
address
Hundred's
Main
0~9
digit
address
setting
mode
SEG10
-
Details
No RMC
address
RMC
address
setting
mode
SEG5
Tens' digit of an address Unit digit of an address
Indication
Details
Indication
0~9
Tens' digit
0~9
SEG11
Group channel(*16)
Group address
Indication
Details
Indication
RMC1
0~2
RMC2
SEG6
Details
A unit digit
SEG12
Details
0~F

Advertisement

Table of Contents
loading

Table of Contents