Installing In/Out Sensor; Selecting The Location Of Eva_In/Out Sensor; Example Of Room Temperature Sensor Installation - Samsung MCM-D201N Installation Manual

Ahu kit
Table of Contents

Advertisement

Installing an AHU KIT

Installing IN/OUT sensor

1. Attach the EVA IN sensor after the distributor and on the lowest temperature pipe of a heat exchanger.
2. Install the EVA OUT sensor 200 mm after the header of AHU heat exchanger as shown in the picture.
3. Insulate the EVA IN and OUT sensor so that it is not affected by wind.
4. Install the ROOM temperature sensor on the RA(Return Air) path of AHU.

Selecting the location of EVA_IN/OUT sensor

Header

Example of ROOM temperature sensor installation

Return air
Exhaust air
Location of room temperature sensor
• In principle, the sensor holder of EVA IN/OUT sensor should be welded at the designated place and then the EVA
IN/OUT sensor should be fixed with a clip.
NOTE
• EVA IN/OUT sensor should be installed at the place where temperature of the heat exchanger air inlet or outlet
can be measured accurately.
16
Distributor
1 EVA IN sensor
2 EVA OUT sensor
Supply air
Outdoor air
❋ Refrigerant flow
Cool mode
Heat mode