Test
IEC 61000-4-9
Pulse Magnetic Field
IEC 61000-4-11
Voltage Dips & Interrupts
IEC 61000-4-16
Mains Frequency Voltage
IEC 61000-4-17
IEC 61000-4-18
Damped Oscillatory Wave
IEC 61000-4-29
IEC 60255-5
a
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RX1400 meets Class 1 requirements for copper ports, which allows
for temporary communication loss.
Test
IEEE 1613
Fast Transient (SWC)
RUGGEDCOM RX1400
Installation Manual, 09/2019, C79000-G8976-1103-13
Description
Ripple on DC
Power Supply
Voltage Dips
and Interrupts
Dielectric Strength
HV Impulse
Description
HV Impulse
Dielectric Strength
Oscillatory (SWC)
Radiated RFI
ESD
6.2 EMC and Environmental Type Tests
Enclosure Ports
AC Power Ports
Signal Ports
DC Power Ports
DC Power Ports
Slow Damped
DC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
Signal Ports
DC Power Ports
Signal Ports
DC Power Ports
Signal Ports
DC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Test Levels
1000 A/m for 1 s
300 A/m
30% for 0.5 Cycles
60% for 5 Cycles
100% for 250 Cycles
30 V Continuous
300 V for 1s
10%
2.5 kV Common
100 kHz or 1 MHz
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV
5 kV
Test Levels
5 kV
2828 VDC or 2 kV
± 4 kV @ 2.5 kHz, 5 kHz
2.5 kV Common mode @1 MHz
2.5 kV Common Mode
1 kV Differential Mode @ 1 MHz
35 V/m
± 8 kV
± 15 kV
Certification
Severi-
ty Levels
4
 
4
3
3
 
 
55