Solar; 3812 F Charg Temp Min Dhw St Tank; 3813 O Temp Diff On Buffer; 3814 O Temp Diff Off Buffer - Siemens Albatros2 RVA78.690 User Manual

Solar compact controller
Hide thumbs Also See for Albatros2 RVA78.690:
Table of Contents

Advertisement

Circulating pump cycling
Circulation setpoint
Siemens
Building Technologies
6.5.5
Circulating pump
Line no.
Operating line
1660
Circulating pump release
24h / day
Switching program
1661
Circulating pump cycling
1663
Circulation setpoint
When the function is activated, the circulating pump is switched on for a fixed time
of 10 minutes within the release time and then switched off again for 20 minutes.
If a sensor is installed in the DHW distribution pipe, the controller monitors its
actual value during the period of time the legionella function is performed. The
adjusted setpoint must be maintained at the sensor during the adjusted "Dwelling
time".
6.6

Solar

6.6.1
Charging controller (dT)
Line no.
Operating line
3810
Temp diff on (DHW storage tank)
3811
Temp diff off (DHW storage tank)
3812
Charg temp min DHW st tank
3813
Temp diff on buffer
3814
Temp diff off buffer
3815
Charging temp min buffer
For charging the storage tank via the heat exchanger, the temperature differential
between collector and storage tank and collector must achieve the minimum
charging temperature for the corresponding storage tank.
T
On
OFF
Tkol
Collector temp
On / Off Collector pump
SdOn Temperature differential on
SdOff Temperature differential off
TSp
Storage tank temperature (DHW storage tank or buffer)
TLmin Charging temp. min (DHW storage tank or buffer)
Setting - - - in operating lines 3813 and 3814, adopts the general temperature
differential of solar operating lines 3810 and 3811.
Solar compact controller
The settings in detail
Tkol
SdEin
SdAus
TSp
TLmin
t
CE1U2396en
18.08.2010
27 / 64