Vent Termination Requirements - Regency Greenfire GF55 Manual

Hide thumbs Also See for Greenfire GF55:

Advertisement

GF55 Wood Pellet Stove
Letter
Minimum Clearance
A
B
C
D
E
F
G
H
3 ft (91 cm) within a height of 15 ft (4.5 m)
above the meter/regulator assembly
I
J
K
L
D
1. Do not terminate the vent in any enclosed or semi-enclosed areas such as a carport, garage, attic, crawlspace, narrow walkway, closely fenced
area, under a sundeck or porch, or any location that can build up a concentration of fumes such as stairwells, covered breezeway, etc.
2. Vent surfaces can become hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.
3. Termination must exhaust above the inlet elevation. It is recommended that at least fi ve feet of vertical pipe be installed outside when the appli-
ance is vented directly through a wall, to create some natural draft to prevent the possibility of smoke or odor during appliance shut down or power
failure. This will keep exhaust from causing a nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest
and preferred venting method is to extend the vent through the roof vertically.
4. Distance from the bottom of the termination and grade is 12" (30 cm) minimum. This is conditional upon the plants and nature of grade surface.
The exhaust gases are hot enough to ignite grass, plants and shrubs located in the vicinity of termination. The grade surface must not be lawn.
5. If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior of the house might occur. Since these
factors are beyond the control of FPI, we grant no guarantee against such incidents.
NOTE: Venting terminals shall not be recessed into walls or siding.
4

VENT TERMINATION REQUIREMENTS

24 in (61 cm)
Above grass, top of plants, wood, or any other combustible materials.
48 in (122 cm)
From beside/below any door or window that may be opened.
24 in (61 cm)
From above any door or window that may be opened.
24 in (61 cm)
To any adjacent building, fences and protruding parts of the structure.
24 in (61 cm)
Below any eave or roof overhang
12 in (30 cm)
To outside corner.
12 in (30 cm)
To inside corner, combustible wall (vertical and horizontal terminations).
To each side of center line extended above natural gas or propane meter/
regulator assembly or mechanical vent.
3 ft (91 cm)
From any forced air intake of other appliance
12 in (30 cm)
Clearance to non-mechanical air supply inlet to building, or the combustion air
inlet to any appliance.
24 in (61 cm)
Clearance above roof line for vertical terminations.
7 ft (2.13 m)
Clearance above paved sidewalk or paved driveway located on public property.
Opens
F
Opens
B
A
Termination Cap
G
Gas Meter
Air Supply Inlet
Gas Inbuilt
Description
B
G
I
Restriction Zone
(Termination not allowed)
G
K
E
G
C
L
Opens
H
March 2008 Product Specifi cations Book