Dimensions, weights and free space requirements
■
Dimensions and weights
See the dimension drawing.
■
Free space requirements
The values are as required by cooling, maintenance and/or operation of the pressure relief
(if present).
Front
mm
1500
Losses, cooling data and noise
ACS880-207LC-...
U
= 690 V
N
0360A-7
0400A-7
0450A-7
0480A-7
0560A-7
0620A-7
0700A-7
0770A-7
0930A-7
1090A-7
1180A-7
1360A-7
1500A-7
1800A-7
2020A-7
2220A-7
2670A-7
2930A-7
3320A-7
3840A-7
4360A-7
5240A-7
5810A-7
1) Measured in a hemi-anechoic room in accordance with ISO 9614-2 standard.
in
mm
5.90
0
Coolant flow
l/min
US gal/min
52
13.7
52
13.7
52
13.7
52
13.7
52
13.7
52
13.7
52
13.7
52
13.7
88
23.2
88
23.2
88
23.2
88
23.2
88
23.2
144
38.0
144
38.0
144
38.0
160
42.3
160
42.3
216
57.1
264
69.7
280
74.0
296
78.2
312
82.4
Sides
in
0
Heat dissipation
into coolant
into air (kW)
(kW)
8.9
0.2
9.8
0.3
11.1
0.3
12.0
0.3
14.1
0.4
15.7
0.4
18.4
0.5
20.9
0.5
21.3
0.5
25.3
0.6
28.6
0.7
31.0
0.8
35.1
0.9
39.3
1.0
45.6
1.2
51.7
1.3
58.6
1.5
66.2
1.7
73.8
1.9
83.8
2.1
100.6
2.6
113.9
2.9
130.3
3.3
Technical data 95
Above
mm
in
250
9.85
Coolant
1)
quantity
Noise
(total)
l
dB(A)
8.1
58
8.1
58
8.1
58
8.1
58
8.1
58
8.1
58
8.1
58
8.1
58
11.3
59
11.3
59
11.8
59
11.8
59
11.8
59
18.7
61
18.7
61
18.7
61
23.6
61
23.6
61
30.0
62
34.1
63
37.4
63
43.3
64
46.6
64