Maintenance and component replacement intervals are based on the assumption that the
equipment is operated within the specified ratings and ambient conditions. ABB recommends
annual drive inspections to ensure the highest reliability and optimum performance.
Note:
Long term operation near the specified maximum ratings or ambient conditions may require
shorter maintenance intervals for certain components. Consult your local ABB Service
representative for additional maintenance recommendations.

Maintenance timers and counters

The control program has maintenance timers and counters that can be configured to generate
a warning when a pre-defined limit is reached. Each timer/counter can be set to monitor
any parameter. This feature is especially useful as a service reminder. For more information,
see the firmware manual.

Cabinet

Cleaning the interior of the cabinet

WARNING!
Read the safety instructions given in Safety instructions for ACS880
liquid-cooled multidrive cabinets and modules (3AXD50000048633
[English]). If you ignore them, injury or death, or damage to the equipment
can occur.
WARNING!
Use a vacuum cleaner with an antistatic hose and nozzle, and wear a grounding
wristband. Otherwise an electrostatic charge might build up and damage the circuit
boards.
1. Stop the drive and do the steps in section
you start the work.
2. Open the cabinet door.
3. Clean the interior of the cabinet. Use a vacuum cleaner and a soft brush.
4. Clean the air inlets of the fans and air outlets of the modules (top).
5. Clean the air inlet gratings (if any) on the door.
6. Close the door.
Electrical safety precautions (page 35)