Ethernet/Ip: Configuration Error; Cavitation Protection Failure; Cavitation Protection Warning; Mpc Operating Time Limit Exceeded - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Cause:
A consistency error was detected when activating the configuration (p8925) for the PROFINET interface. The currently set
configuration has not been activated.
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.
Note:
DHCP: Dynamic Host Configuration Protocol
Remedy:
- check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925).
or
- reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).
A50011 (F)

Ethernet/IP: configuration error

Reaction:
NONE
Acknowledge:
NONE
Cause:
An EtherNet/IP controller attempts to establish a connection using an incorrect configuring telegram.
The telegram length set in the controller does not match the parameterization in the drive device.
Remedy:
Check the set telegram length.
For p0922 not equal to 999, then the length of the selected telegram applies.
For p0922 = 999, the maximum interconnected PZD (r2067) applies.
See also: p0922 (PROFIdrive PZD telegram selection), r2067 (PZD maximum interconnected)
F52960

Cavitation protection failure

Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Conditions exist for cavitation damage. Cavitation damage is damage caused to a pump in pumping systems when the fluid
is not flowing sufficiently. This can lead to heat build up and subsequent damage to the pump.
Remedy:
If cavitation is not occurring, reduce the cavitation threshold p29626, or increase the cavitation protection delay. Ensure
sensor feedback is working.
A52961

Cavitation protection warning

Reaction:
NONE
Acknowledge:
NONE
Cause:
Conditions for possible cavitation damage are detected.
Remedy:
See F52960.
A52962

Mpc operating time limit exceeded

Reaction:
NONE
Acknowledge:
NONE
Cause:
The continuous operating time of at least one motor has exceeded the limit.
Remedy:
Incease p29531 or set p29547 = 0.
A52963
Mpc PID deviation exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The PID deviation (p2273) has exceeded the threashold (p29544) and all motors are running except the motors under
service or locked.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Warnings, faults and system messages
9.6 List of fault codes and alarm codes