Product Specification; Specification - Daikin VAM 350GJVE Service Manual

Heat reclaim ventilation
Hide thumbs Also See for VAM 350GJVE:
Table of Contents

Advertisement

Product Specification

1.
Product Specification
1.1

Specification

Model name
Power supply
Temperature exchange efficiency
Enthalpy
Cooling
exchange
efficiency
Heating
Casing
Insulation material
Dimensions
Heat exchange system
Heat exchange element
Air filter
Fan
Type
Air flow
Heat
rate
exchange
mode
External static pressure Ultra-High
Fan motor
Motor output
Operating
Heat exchange mode
sound
Bypass mode
Operation range (Ambient)
Connection duct diameter
Weight
Drawing number
Test conditions are as follows.
Note:
1. Operation sound is measured at 1.5 m below the center of the body.
2. Air flow rate can be changed over to Low mode or High mode.
3. Normal AMP., input, efficiency depend on the other above conditions.
4. Operating sound is measured in an anechoic chamber.
5. The sound level at the air discharge port is about 8 dB higher than the unit's operating sound.
6. The specifications, designs and information here are subject to change without notice.
7. Temperature Exchange Efficiency is the mean value in cooling and heating.
8. Efficiency is measured under the following conditions.
6
Ultra-High
%
High
%
Low
%
Ultra-High
%
High
%
Low
%
Ultra-High
%
High
%
Low
%
H × W × D
mm
278 × 810 × 551
3
Ultra-High
m
/ h
3
High
m
/ h
3
Low
m
/ h
Pa
High
Pa
Low
Pa
Type
kW
Ultra-High
dBA
High
dBA
Low
dBA
Ultra-High
dBA
28.5 – 29.5 / 29.5
High
dBA
27.5 – 28.5 / 28.5
Low
dBA
mm
kg
Condition
Cooling condition
Heating condition
Operating sound level generally may become greater than this value depending on the operating
conditions, reflected sound, and peripheral noise.
Ratio of rated external static pressure has been kept as follows. Outdoor side to indoor side = 7 to 1
VAM150GJVE
VAM250GJVE
Single phase 220 – 240 V / 220 V, 50 / 60 Hz
79 / 79
79 / 79
84 / 85
66 / 66
66 / 66
70 / 70.5
72 / 72
72 / 72
76 / 76.5
Galvanized steel plate
Self-extinguishable urethane foam
278 × 810 × 551
Air to air cross flow total heat (sensible heat + latent heat) exchange
Specially processed nonflammable paper
Multidirectional fibrous fleeces
150 / 150
150 / 150
100 / 95
120 / 154
106 / 131
56 / 60
Open type capacitor permanent split-phase induction motor, 4 poles × 2
0.030 × 2
27 – 28.5 / 28.5
26 – 27.5 / 27.5
20.5 – 21.5 / 21
28.5 – 30.5 / 30.5
27.5 – 29 / 29.5
22.5 – 23.5 / 22
22.5 – 23 / 22.5
–15°C to 50°CDB (80% RH or less)
φ 100
24
C : 4D051116
Indoor
°CDB
R·H (%)
27
50
20
40
VAM350GJVE
75 / 75
75 / 75
79 / 79
63 / 63
63 / 63
66 / 66
71 / 71
71 / 71
74 / 74
306 × 879 × 800
Sirroco fan
250 / 250
250 / 250
155 / 155
70 / 96
54 / 65
24 / 20
0.030 × 2
27 – 29 / 29
31.5 – 33 / 33
26 – 27.5 / 28
30 – 31.5 / 30
21 – 22 / 21
33 – 34.5 / 34.5
31.5 – 33 / 31.5
24.5 – 26.5 / 24.5
φ 150
24
C : 4D051117
C : 4D051118
Outdoor
°CDB
35
7
Product Specification
Si71-502
(50 / 60Hz)
79 / 79
79 / 79
82 / 82
66 / 66
66 / 66
70 / 70
70 / 70
70 / 70
77 / 77
350 / 350
350 / 350
230 / 230
169 / 222
141 / 145
67 / 30
0.090 × 2
23 – 25 / 23
φ 150
32
R·H (%)
60
70

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents