Adjustable Parameters; Operating Modes - Emerson Rosemount 326T Quick Start Manual

Temperature transmitter
Table of Contents

Advertisement

Operation
January 2019
information about the required IO-Link hardware and software are available at
Emerson.com/Rosemount
3.3

Adjustable parameters

Use IO-Link software to configure these parameters.
Parameter
OU2
ASP2
AEP2
COF
FOU2
Uni
Update rate of display
Orientation of display
3.4

Operating modes

The temperature transmitter uses different operating modes depending on the measured
temperature.
After turning on the temperature transmitter the temperature transmitter displays the
current measured temperature and the analog output provides a signal proportional to
the measured temperature.
If the temperature is outside of the measuring range the temperature transmitter displays
OL or UL.
10
Description
Output function: analog signal is 4-20 mA (I) or 20-4 mA (Ineg)
Analog start point for the measured temperature value.
Analog end point for the measured temperature value. The minimum
difference between ASP2 and AEP2 is 9 °F (5 °C).
Zero point calibration. Offsets the zero point ± 18 °F in steps of .18 °F (±
10 °C in steps of 0.1 °C).
Behavior of the output after a fault.
ON: the analog signal is driven to 21.1 mA.
OFF: the analog signal is driven to 3.5 mA.
Sets the temperature unit in °F or °C.
The rate at which the transmitter updates the displayed temperature
measurement.
d1: 50 ms
d2: 200 ms
d3: 600 ms
rd: rotates the display by 180°.
Quick Start Guide
00825-0100-4328
Quick Start Guide