Rheem W2W Series Owner's Manual And Installation Instructions page 58

Commercial water to water heat pump water heater
Table of Contents

Advertisement

The commissioning procedure MUST be performed in the order shown.
st
1
Heat Pump- Master
1.
Ensure all heat pumps are turned OFF at the isolating switch.
2.
Turn ON slave 1 heat pump (2
3.
Configure heat pump address.
 Whilst in the home screen on control panel, simultaneously press and hold
Up
, Down
 Use Up
 Press and release Enter
 Change the following values as shown below.
Menu
Slave 1
Display
17
address
setting
I/O board
02
address
trm1
32
trm2
17
trm3 None
Yes
– Ok?
 Press "Enter"
screen and settings will be saved.
nd
2
Heat Pump
nd
and Enter
or Down
buttons to set values.
to move curser to next line.
Slave 2
Slave 3
18
19
03
04
32
32
18
19
Yes
Yes
to confirm settings. The screen will change to the home
rd
3
Heat Pump
heat pump).
for 5 seconds to enter the setup menu.
Master
Example Screen Image of Slave 1
16
01
32
16
Yes
58
th
4
Heat Pump