Application Data; Operating Range; Minimum Chilled Water Flow (Units Without Hydraulic Module); Maximum Chilled Water Flow (Units Without Hydraulic Module) - Carrier Aquaforce 30XAS Series Installation, Operation And Maintenance Instructions

Air-cooled liquid chillers. nominal cooling capacity: 232-486 kw - 50 hz
Hide thumbs Also See for Aquaforce 30XAS Series:
Table of Contents

Advertisement

6 - APPLICATION DATA

6.1 - Operating range

30XAS standard unit
Evaporator leaving water temperature, °C
30XAS unit with option 119
Evaporator leaving water temperature, °C
Legend:
Operating range, unit equipped with option 28 (winter operation).
Below 0 °C air temperature the unit must either be equipped with the evaporator
frost protection option (41A or 41B), or the water loop must be protected against 
frost by using a frost protection solution (by the installer).
Part load average
Operating range, unit equipped with option 28 (winter operation).
Below 0 °C air temperature the unit must either be equipped with the
evaporator frost protection option (41A or 41B), or the water loop must be 
protected against frost by using a frost protection solution (by the installer).
Part load average
18
Evaporator water temperature, °C
Water entering temperature at start-up
Water entering temperature during operation
Water leaving temperature during operation
Note: If the leaving water temperature is below 4 °C, a glycol/water solution or the
frost protection option must be used.
Condenser air temperature, °C
Storage
Operation, standard unit
With winter operation option (option 28)
Operation, with high energy efficiency (option 
119)
(3)
Note: If the air temperature is below 0 °C, a glycol/water solution or the frost protection
option must be used.
(1) Based on the installation type and the air temperature
(2)  Part load, based on the water temperature
(3) Recommended for operation above 46 °C
(4) Part-load operation
6.2 - Minimum chilled water flow (units without
hydraulic module)
The minimum chilled water flow is shown in the table on the next 
page. If the system flow is less than this, the evapo-rator flow can 
be recirculated, as shown in the diagram.
For minimum chilled water flow rate
Legend
1
Evaporator
2
Recirculation
6.3 - Maximum chilled water flow (units without
hydraulic module)
The maximum chilled water flow is shown in the table on the next 
page. If the system flow exceeds the maximum value, it can be 
bypassed as shown in the diagram.
For maximum chilled water flow rate
Legend
1
Evaporator
2
Bypass
Minimum Maximum
-
45
6,8
21
3,3
15
Minimum Maximum
-20
68
-10
55
-20
55
-10
55
1
2
1
2
(1)
(2)
(2)
(4)