Appendix; Appendix A. Instructions Converted By Change Model On Cx-Programmer - Omron C200HS Series Replacement Manual

From c200hs to cj2
Hide thumbs Also See for C200HS Series:
Table of Contents

Advertisement

7.

Appendix

Appendix A. Instructions converted by Change Model on CX-Programmer.

(1) The data type of operand is changed from BCD to binary for some instructions.
(2) The number of operands is changed for some instructions.
(3) Interrupt control instructions must be changed. (Use MSKS, MSKR, CLI, DI, and EI).
Refer to the list below for details. The table lists the instructions which differ between before and after conversion. The other
instructions remain unchanged after conversion.
Instruction for C200HS
JMP(04)
JMP(004) or
JMP0(515)
JME(05)
JME(005) or
JME0(516)
WSFT(16)
Same as C200HS
FUN17
ASFT(017)
XFER(70)
XFERC(565)
MOVB(82)
MOVBC(568)
DIST(80)
DISTC(566)
COLL(81)
COLLC(567)
FUN60
CMPL(060)
FUN19
MCMP(019)
FUN63
LINE(063)
FUN64
COLM(064)
FUN65
SEC(065)
FUN66
HMS(066)
INC(38)
++B(594)
DEC(39)
--B(596)
ADD(30)
+B(404)
ADDL(54)
+BL(405)
SUB(31)
-B(414)
SUBL(55)
-BL(415)
MUL(32)
*B(424)
MULL(56)
*BL(425)
DIV(33)
/B(434)
DIVL(57)
/BL(435)
ADB(50)
+(400)
SBB(51)
-(410)
MLB(52)
*(420)
DVB(53)
/(430)
FUN69
APR(069)
FUN89
Not supported
STEP(08)
Same as C200HS
SNXT(09)
Same as C200HS
Use a differentiated
execution condition
for the SNXT
instruction.
FAL(06)
Same as C200HS
FALS(07)
Same as C200HS
MSG(46)
MSG(046)
FUN47
Not supported
FUN67
BCNTC(621)
WDT(94)
WDT(094)
FUN61
Not supported
FUN18
Enter the settings in the PLC Setup.
FUN48
Not supported
FUN49
Enter the settings in the PLC Setup.
FUN90
SEND(090)
FUN98
RECV(098)
16
Instruction for CJ2
When #0 is set to the operand, JMP is converted to
JMP0 and the operand is deleted.
If a value other than #0 is set, the operand is the same.
When #0 is set to the operand, JME is converted to
JME0 and the operand is deleted.
If a value other than #0 is set, the operand is the same.
#0 is added to the first operand.
WSFT St E → WSFT #0 St E
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Changed from BCD data to binary data.
Changed from BCD data to binary data.
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Same as C200HS
Combine and use the following instructions: MSKS(690), CLI(691), MSKR(692),
DI(693), EI(694)
The CIO, Holding, Work, Auxiliary, Link Areas are all
converted into the Work Area.
Same as C200H
#0 is added to the second operand.
FAL N
#0 is added to the second operand.
FALS N
#0 is added to the first operand.
MSG FM
The number of characters (words) to be registered
from the first message word is changed from 16
characters (8 words) to 32 characters (16 words).
Use MSG(046) instead.
Same as C200HS
Control data configuration is changed.
Use IORF (097) instead.
Control data configuration is changed.
Control data configuration is changed.
Operand
FAL N #0
FALS N #0
MSG #0 M
Number of operands
#0: Changed from 1 to 0
<> #0: Same
#0: Changed from 1 to 0
<> #0: Same
Changed from 2 to 3
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Same
Changed from 1 to 2.
Changed from 1 to 2.
Changed from 1 to 2.
Same
Same
Same
Same

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents