Omron C200HS Series Replacement Manual page 14

From c200hs to cj2
Hide thumbs Also See for C200HS Series:
Table of Contents

Advertisement

XW2Z-S011
CJ1W-OD231
C200H-OD215
Reused cable
Rated voltage
5 to 24 VDC
16 mA/4.5 VDC to
100 mA/26.4 VDC
Max. switching capacity
0.8 A/common,
3.2 A/Unit
Leakage current
0.1 mA max.
Residual voltage
0.7 V max.
ON response time
0.2 ms max.
OFF response time
0.6 ms max.
8 points/common x
No. of circuits
4 circuits (32 outputs)
Fuses
4 (1 fuse/common)
5 to 24 VDC±10%,
90 mA min.
External power supply
2.8 mA x no. of ON outputs
Dynamic outputs
30 mA min.
C200H-OD215
12 to 24 VDC
0.5 A/point,
2 A/common, 4 A/Unit
0.1 mA max.
1.5 V max.
0.1 ms max.
0.8 ms max.
16 points/common x
2 circuits (32 outputs)
None
10.2 to 26.4 VDC,
30 mA min.
Not supported
CJ1W-OD231
We recommend you to use 24 VDC instead if 5 VDC
is used.
Make sure that the connected device operates
correctly.
Make sure that the connected device operates
correctly.
Make sure that the connected device operates
correctly.
The number of circuits decreased from 4 to 2.
Rewire if separate power supplies are used.
When protection is required, connect a protective
device externally.
Dynamic outputs are not supported.
* CN1 COM0 and COM1 and
CN2 COM2 and COM3 are
internally connected in the
CJ-series Unit. When separate
power supplies were used,
rewire to use one common
power supply.
Remarks
5

Hide quick links: