Optional Accessories; Selecting Installation Location - Samsung DVM S ECO AM XMDG Series Installation Manual

Table of Contents

Advertisement

AA Preparations for Installation

Optional accessories

The following accessories are needed when connecting the outdoor and indoor unit.
❇ ❇
Model
Y-joint
Distribution header
❇ ❇
Refrigerant distributor component has to be installed when connecting indoor unit with no built-in EEV (electronic
expansion valve)

Selecting installation location

Decide the installation location, with the consideration of the following conditions, under user
f
X
Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in residential
areas, keep the operation hours in mind.)
f
X
Place where structure can bear the weight and vibration of the outdoor unit.
f
X
Place with flat surface where rainwater does not settle or leak.
f
X
Place where it is not exposed to strong wind.
f
X
Well ventilated place with sufficient service place for repairs and maintenance. (Discharge duct can be purchased
separately)
f
X
Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance.
f
X
Place where it allows easy waterproofing and draining work for the condensation water generated from the outdoor
unit during heating operation.
f
X
Place where there is no risk of inflammable gas leakage.
f
X
Place where there is no direct influence of snow or rain.
f
X
Do not install the product in a place where it will be directly exposed to sea breeze.
-
Consult an installation expert (or company) since you will need to take extra anti-corrosion measures if you need to
install the product in a place where it can be exposed to direct sea breeze. (You have to remove dusts and salinity on
the heat exchanger and apply designated rust inhibitor more than once a year.)
f
X
If the outdoor unit is installed in the location where it can be attacked by high wind, please pay attention to these
issues:
-
Caution when outdoor unit air outlet side was blow by high wind that speed over 5m/s, Because the outlet air was
suctioned in once again, reduce the airflow of machine, and may cause these appearance:
-
Lower capacity; -severe frost in heating mode; - machine break down for high pressure .
f
X
If the air outlet side of the outdoor unit encountered a large continuous strong wind blowing, the fan will run reversely
with high speed, and may be damaged by it. so please refer to the installation instruction.
Model
MXJ-YA1509M
MXJ-YA2512M
MXJ-HA2512M
MXJ-HA3115M
Total capacity
15.0 kW and below
Over 15.0 kW ~ 40.0 kW and below
45.0 kW and Below (for 4 rooms)
70.3 kW and below (for 8 rooms)
'
s approval.
7