Insulate The Distribution Header - Samsung DVM S ECO AM XMDG Series Installation Manual

Table of Contents

Advertisement

Pipe insulation
AA

Insulate the distribution header

f
X
Fix the distribution header with a cable tie and cover the connected part.
f
X
Insulate the distribution header and the welded part and wrap the connected part with an
adhesive insulation tape to prevent dew formation.
Adhesive insulation tape
Insulate the refrigerant
Insulate the
pipe
distribution header
f
X
Fix the distribution header with a hanger after insulating it.
Insulating the branchjoint
f
X
Tightly attach the insulator, provided with the branch joint, to the separately purchased insulator. Wrap the connected
part with an insulator (separately purchased item) that has thickness of at least 10mm.
f
X
Use an insulator that resist heat up to 120
10mm.
Pipe insulator
(Separately
Provided Insulator
purchased item)
Fix securely without
any gap.
150mm
Branch joint
Thickness of the insulator (Separately purchased
item) should be thicker than 10mm.
46
°
C. Wrap the branch joint with an insulation that has thickness of at least
Fix securely without any gap.
Pipe insulator (Separately
purchased item)
Insulate after welding a stopper
Adhesive insulation tape
Insulation tape (Separately purchased item)
Pipe
Pipe insulator (Separately purchased item)
❇ ❇
Attach the adhesive insulation tape to
the pipe, as shown in the picture, after
insulating the pipe.
Insulation