Wiring work

AA

Specification of the circuit breaker and power cable

DVM S ECO Series
Capacity (HP)
8
9
8
❇ ❇
MCA: Minimum Circuit Ampere;
❇ ❇
MFA: Maximum Fuse Ampere
❇ ❇
Please refer to the MCA specification to selecte the line parameter.
❇ ❇
Please refer to the MFA specification to selecte the MCCB and ELB specification.
❇ ❇
Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 66 / CENELEC: H07RN-F)
• This device is intended for the connection to a power supply system with a maximum permissible system impedance
shown in the table (on the left page) at the interface point (power service box) of the user
• The user must ensure that this device is connected only to a power supply system which fulfills the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
Ssc(*2) at the interface point between the user
or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the
equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc(*2).
• [Ssc (*2)]
Capacity (HP)
8
Caution for electrical work
• You must install ELCB or MCCB + ELB
Caution
-
ELCB: Earth leakage breaker
-
MCCB: Molded case circuit breaker
-
ELB: Earth leakage breaker
• Do not operate the outdoor unit before completing the
• refrigerant pipe work.
• Do not disconnect or change the cable inside the product. It may cause damage to the product.
• Specification of the power cable is selected based on following installation condition; culvert installation/
ambient temperature 30
please consult an electrical installation expert and re-select the power cable.
-
If the length of power cable exceed 50m, re-select the power cable considering the voltage drop.
• Use a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outer
cover).
• Do not use the power cable with the core wire exposed due to insulator damage occurred during removal of
the sheath. When the core wire is exposed, it may cause fire.
Model
AM080FXMDG
AM090FXMDG
AM080MXMDG
'
s supply and the public system. It is the responsibility of the installer
Model
AM080XMDG
°
C/ single multi conductor cables. If the condition is different from the ones stated,
MCA (A)
18.0
18.5
18.4
'
s supply.
Ssc [MVA]
3.4
Exposed
core
(Example of exposed core)
MFA (A)
25.0
25.0
25.0
Insulator
(Inner
cover)
Sheath
(Outer
cover)
33