Bristol ControlWave Micro
Wiring plan
Fig. 48: Connection of SITRANS LG260 to RTU Bristol ControlWave Micro
1
SITRANS LG260
2
RTU Bristol ControlWave Micro
3
Voltage supply
Parameter
Parameter
Baud Rate
Floating Point Format Code
RTU Data Type
Input Register Base Number
The basic number of the input registers is always added to the input register address of SITRANS
LG260.
Address 1303 must hence be entered as register address for 1302 for RTU Bristol ControlWave
Micro.
86
1
+8
+30 Vdc
to
GND
3
SITRANS LG260 - Operating Instructions
RS 485 on COM1
1 +SV
2 RX-
3 TX-
4 GND
5 RXT
6 TXT
7 not used
8 not used
2
Value
9600
2 (FC4)
32-bit registers as 2 16-bit registers
1
PBD-51041059