CPU 314 IFM
The following addresses are assigned to the integrated I/O of CPU 314 IFM:
Table 7-2
Inputs/Outputs
20 digital inputs
16 digital outputs
4 analog inputs
1 analog output
CPU 312C
The following addresses are assigned to the integrated I/O of CPU 312C:
Table 7-3
Inputs/Outputs
10 digital inputs
6 digital outputs
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01

Integrated I/O of CPU 314 IFM

Addresses
124.0 to 126.3
of those are 4 Inputs for
integrated functions:
126.0 to 126.3
124.0 to 125.7
128 to 135
128 to 129
Integrated I/O of CPU 312C
Default: addresses
124.0 to 125.1
of those are 8 Inputs for
technological functions:
124.0 to 124.7
124.0 to 124.5
of those are 2 Inputs for
technological functions:
124.0 to 124.1
Remarks
Optional utilization of Inputs for
integrated functions:
Counting
Counting A/B
Frequency measurement
Positioning
Interrupt input
Refer to the Manual
Integrated functions
Remarks
All digital inputs can be programmed
as interrupt input.
Optional technological functions:
Counting
Frequency measurement
Pulse width modulation
Addressing
7-7