Structure Of Station Status 3 (Byte 2) - Siemens SIMATIC S7-300 Hardware And Installation Manual

Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Testing functions, Diagnostics and Fault Elimination
Station Status 3
Table 10-15 Structure of Station Status 3 (Byte 2)
Bit
0 to 6
0: These bits are always "0"
7
1:The DP slave is out of memory for received diagnostic messages.
The DP master cannot write all diagnostic messages sent by the DP slave to its diagnostic
buffer.
Master PROFIBUS address
The "Master-PROFIBUS address" diagnostic byte stores the DP address of the DP
master:
• that has configured the DP slave and
• has read and write access to the DP slave.
Table 10-16 Structure of the Master PROFIBUS address (byte 3)
Bit
0 to 7
DP address of the DP master that has configured the DP slave and has read/write access to
that DP slave.
FFH: DP slave was not configured by a DP master
Manufacturer ID
The manufacturer ID contains a code specifying the DP slave's type.
Table 10-17 Structure of the manufacturer ID (byte 4 and 5)
Byte 4
80
2F
H
80
6F
H
80
7F
H
80
DO
H
80
D1
H
10-24
Description
Description
Byte 5
CPU 315-2-DP
H
CPU 316-2-DP
H
CPU 318-2
H
313C-2-DP
H
314C-2-DP
H
Manufacturer ID for
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01