Facing
1. Combustible wall (such as drywall panels) must be installed flush with
the fireplace. It may not project in front of and on the fireplace (i.e.
the steel facade of the fireplace (see Figure 17).
2. Decorative frame made of combustible material cannot project in front
of and on the fireplace steel front, in the space delimited by the width
of the unit (38") and a height of 54" from the base of the appliance
(see Figure 19).
3. Non-combustible materials such as brick, stone or ceramic tile may
project in front of and onto the fireplace facing (see Figure 18).
MANTEL
*
54"
Figure 17
Figure 19
1/2" GYPSUMBOARD
2" x 3" MIN.
SPACER
38" (965mm)
54"
(1372mm)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Mantel
The mantel must be installed at least 54" (1372 mm) above the base of
the fireplace (see Figure 17).
*NOTE: Mantel can be reduced to 48" (1219 mm) if the Clean Face Panel
option is installed with the heatflo kit.
NON
COMBUSTIBLE
FACING
Figure 18
Combustible cannot project over
or in front of the fireplace
1/2" GYPSUMBOARD
2" x 3" MIN.
SPACER