Mounting Position, Mounting Clearances; Standard Mounting Position - Siemens SITOP PSU6200 Manual

Hide thumbs Also See for SITOP PSU6200:
Table of Contents

Advertisement

Mounting position, mounting clearances

4.1

Standard mounting position

The device is mounted on standard mounting rails according to EN 60715 35x7,5/15. The
device must be mounted vertically in such a way that the input terminals are at the bottom
and the output terminals are at the top to ensure correct cooling.
A clearance of at least 45 mm must always be maintained above and below the device (max.
cable channel depth, 50 mm).
Lateral clearances do not have to be maintained.
Output current as a function of the ambient temperature and mounting height
Figure 4-1
Figure 4-2
SITOP PSU6200 1ph
Manual, 03.2019, A5E44623264-1-76
6EP3323-7SB00-0AX0 output current in the standard mounting position
6EP3324-7SB00-3AX0 output current in the standard mounting position