Field Settings Table - Daikin EKHBHE008BA3V3 Operation Manual

Indoor unit for air to water heat pump system and options
Hide thumbs Also See for EKHBHE008BA3V3:
Table of Contents

Advertisement

Field settings table

First
Second
code
code
Setting name
0
User permission level
00
User permission level
1
Weather dependent set point
00
Low ambient temperature (Lo_A)
01
High ambient temperature (Hi_A)
02
Set point at low ambient temperature (Lo_TI)
03
Set point at high ambient temperature (Hi_TI)
2
Disinfection function
00
Operation interval
01
Status
02
Start time
03
Set point
04
Interval
3
Auto restart
00
Status
4
Space heating off temperature
00
Installation related setting
01
Installation related setting
02
Space heating off temperature
03
Installation related setting
04
Installation related setting
5
Installation related settings
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
6
Installation related settings
00
Installation related setting
01
Installation related setting
02
Installation related setting
7
Installation related settings
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
8
Installation related settings
00
Installation related setting
01
Installation related setting
02
Installation related setting
03
Installation related setting
04
Installation related setting
EKHBH/XE008BA
Indoor unit for air to water heat pump system and options
4PW56302-1
Installer setting at variance with default value
Date
Value
Date
Default
Value
value
Range
3
2/3
–10
–20~5
15
10~20
40
25~55
25
25~55
Mon~Sun,
Fri
All
1 (ON)
0/1
23:00
0:00~23:00
70
40~80
10
5~60
0 (ON)
0/1
25
14~25
Step
Unit
1
1
°C
1
°C
1
°C
1
°C
1:00
hour
5
°C
5
min
1
°C
Operation manual