4. commissioning

4.3 Ignition procedure

Press the ON/OFF button on the control panel to switch on the
boiler. The display shows:
● the operating mode:
winter
summer
● The fi gures indicate:
- the fl ow temperature in central heating mode
- the set temperature of the hot water in domestic hot
water
The carrying out of certain functions is shown:
Deaeration cycle started
Central Heating Post-circulation
D.H.W. circuit Post-circulation
4.3.1 Electricity supply
- Check that the voltage and frequency of the electricity supply
correspond to the data shown on the boiler data plate;
- Make sure that the earthing connection is effi cient.
30
OK
ESC
Fig. 4.1
4.4 First ignition
1. Make sure that:
- The gas valve is closed;
- The electrical connection has been properly carried out.
Make sure that, in any case, the green/yellow earthing wire
is connected to an effi cient earthing system;
- Use a screwdriver to lift the cap on the automatic air relief
valve;
- Switch on the boiler (by
pressing
the
ON/OFF
button) and use the MODE
button to select the standby
mode, where no hot water
or heating requests are
made.
- Start the deaeration cycle
by pressing the MODE
button for 5 seconds.
The boiler will start a
deaeration cycle lasting
about 7 minutes (See below). If you need to stop it press
the ESC button, alternatively it is possible to manually vent
the heat exchanger.
-
At the end, check that the system is completely deaerated
and, if not, repeat the procedure.
-
Bleed the air from the radiators;
-
The exhaust duct for combustion products should be
suitable and free from any obstructions;
-
Check whether the trap contains water; if not, it must be
refi lled.
N.B.: if the boiler will not be used for long periods,
the trap should be fi lled before the boiler is started up
again. It is dangerous not to refi ll the siphon as fumes
may be released into the environment.
2. Open the gas cock and check the connection seals,
including the boiler connection joints, making sure that
the meter does not detect any passage of gas. Repair any
leaks.
3. Start the boiler by selecting the heating or domestic hot
water operation using the MODE button.
4.4.1 Deaeration cycle
During the fi lling stage or if there is excess air in the system,
the deaeration cycle can be activated by holding the MODE
button for 5 seconds. The boiler will start a cycle which lasts
approximately 7 minutes. When this is complete the menu
screen will be restored. The cycle may either be repeated, if
necessary, or stopped by pressing MODE. Press the MODE
button until the normal display screen is restored. I
IS STOPPED BE SURE TO MANUALLY VENT THE APPLIANCE
F THE CYCLE
.