Fuel Requirements
The engine has been fitted with a dual fuel carburetion
system. The unit will run on natural gas or LP gas
(vapor), but it has been factory set to run on natural gas.
The fuel system will be configured for the available fuel
source during installation.
Recommended fuels should have a MJ/BTU content of at
least 37.26 megajoules per cubic meter (1000 BTUs per
cubic foot) for natural gas, or at least 93.15 megajoules per
cubic meter (2500 BTUs per cubic foot) for LP gas (vapor).
NOTE: If converting to LP gas from natural gas, a
minimum LP tank size of 946 L (250 gal) is
recommended. See the installation manual for complete
procedures and details.
Battery Requirements
12 volts, Group 26R-540CCA minimum or Group 35AGM-
650CCA minimum
(not
Maintenance
for proper battery maintenance procedures.
Replacement Parts
Description
26R Exide Battery
Spark Plug
Oil Filter
Air Filter
Control Panel Fuse
Owner's Manual for 50 Hz Air-Cooled Generator Sets
included
with
unit.)
See
8 kVA
0E9368
(RL87YC or equivalent)
0E9371A
Battery Charger
The battery charger is integrated into the control panel
module in all models. It operates as a smart charger,
ensuring
output
charging
continuously optimized to promote maximum battery life.
NOTE: A warning is displayed on the LCD when the
battery needs service.
NOTE: Do not use external battery chargers.
Engine Oil Requirements
See
Engine Oil Requirements
section for proper oil viscosity.
Activating the Generator Set
The generator set should be activated upon initial start-
up. See the installation manual for complete instructions.
Wi-Fi Module
The generator set is equipped with a Wi-Fi module. Refer
to the Wi-Fi module user manual for further instructions.
10 kVA
0H3421S
0G0767A
(RC12YC or equivalent)
070185E
0J8478
0D7178T
General Information
levels
are
safe
and
in the Maintenance
13 kVA
15